Power switchgear and controlgear assembly from 630 to 5,000 A according to DIN EN 61439-1/-2.
Supports your power supply when high demands are placed on the safety, reliability and economic efficiency.
Power switchgear and controlgear assembly from 630 to 5,000 A according to DIN EN 61439-1/-2.
Supports your power supply when high demands are placed on the safety, reliability and economic efficiency.
Rated voltage Ue | |
400 V | 690 V |
Maximum permissible short-circuit current under arcing conditions Ip arc | |
80 kA | 70 kA |
Permissible arc duration tarc | |
300 ms | 300 ms |
The assembly is not available after the arc event. The assembly or damaged parts of the assembly must be replaced.
Rated voltage Ue | |
400 V | 690 V |
Maximum permissible short-circuit current under arcing conditions Ip arc | |
80 kA | 70 kA |
Permissible arc duration tarc | |
300 ms | 300 ms |
The assembly is not available after the arc event. The affected cubicle must be replaced, adjacent cubicles must be checked for damage and cleaned if necessary.
Rated voltage Ue | |
400 V | 690 V |
Maximum permissible short-circuit current under arcing conditions Ip arc | |
100 kA | 100 kA |
Arc quenching time | |
< 3 ms | < 3 ms |
Verification by testing that false tripping is prevented in the event of a switching arc caused by the circuit-breaker | |
yes | no |
The assembly is available again within a short time after eliminating the cause of the fault and replacing the extinguishing equipment. As the effects of the arcing are reduced to a minimum, cleaning is not necessary.
The arc-fault mitigation system monitors the assembly even when the switchgear assembly door is open and offers the greatest possible protection for personnel working on the switchgear assembly.
For safely and flexibly designing your power distribution even according to the future valid standard DIN EN 61439-2 ED3
Couplers in the VAMOCON system are integrated longitudinally into the central main busbar system and installed from the right and left, phase-shifted, at the height of the switch connectors. The spacing between the front and rear busbars, combined with support between them, make the design possible and simultaneously stiffen it.
Our longitudinal couplers are tested up to a short-circuit withstand current (Icw) of 100 kA during one second. Since no complex busbar risers have to be built, and no second cubicle is required, the copper input is reduced by about 120 kg per cubicle compared with a conventional coupler at 3,200 A rated current. The couplers are available up to 5,000 A for 3- and 4-pole main busbar systems.
The system allows forms of internal separation ranging from Form 1 to 4b (DIN EN 61439-2) as well as configurations ranging from free-standing single cubicles and cubicles lined up in rows to corner cubicles (L- and U-shaped) and back-to-back configurations. Two construction heights and a large number of variants enable a wide variety of solutions. Plinths with 100 and 200 mm heights are possible.
Expanded metal cover (0.9 mm), protection degree IP4x
Doors with swing handle and cam locks of your choice
Door with door mounting strips, pocket for circuit diagrams and contact hazard protection IP4XD on request
Plinth with 100 or 200 mm height
180-degree hinge with catch for hanging the door (arc fault-proof)
Compartment floor, support for circuit-breakers, busbar carrier and door hinge all in one
Side panel flush with door at front
Head trim for labelling, also in colour of choice
Standards/Specifications | Power switchgear and controlgear assembly with design verification by testing | EN 61439-1/-2:2011 DIN EN 61439-1/-2:2012-06 VDE 0660-600-1/-2:2012-06 |
Testing under conditions of arcing due to internal fault | IEC/TR 61641:2014 Passive (without arc-fault mitigation system): Ue up to 690 V, Ip arc up to 80 kA, tarc = 300 ms Active (with arc-fault mitigation system): Ue up to 690 V, Ipc arc up to 100 kA |
|
Protection against electric shock | DIN EN 50274, VDE 0660 Part 514 | |
Tested switchgear brands | ABB, Schneider Electric, Siemens, Efen, Jean Müller, Wöhner | |
Degree of protection | EN 60529 | IP2x, IP3x, IP4x |
Protection class |
I (protective earthing) |
|
Rated current (ln) |
up to 5,000 A |
|
Rated impulse withstand voltage (Uimp) |
8 KV |
|
Overvoltage category |
IV |
|
Degree of pollution |
3 |
|
Rated peak withstand current (lpk) | Main busbars (3- and 4-pole) |
up to 330 kA |
Rated short-time withstand current (lcw) | Main busbars (3- and 4-pole) | up to 150 kA / 1 sec. |
Rated frequency (f) |
50 to 60 Hz |
|
Rated insulation voltage ( Ui) |
Main circuit |
1,000 V |
Rated operational voltage (Ue) |
Main circuit |
up to 690 VAC |
Internal separation | Form 1 to 4b, depending on the cubicle type | |
Mechanical strength |
IEC 62262 |
up to IK10 |
Ambient temperature and installation | -5°C to +40°C (average over 24h: 35°C), indoor installation, Installation altitude up to 2000 m above normal altitude |
|
Cooling / ventilation | Self-convection or forced ventilation | |
Materials and surfaces | Frame components, interior fittings | Sheet steel, 2.0 - 3.0 mm, galvanised |
Doors |
Sheet steel, 2.0 mm, galvanised, powder-coated |
|
Side panels |
Sheet steel, 1.5 mm, galvanised, powder-coated |
|
Rear panels, roof plates | Sheet steel, 1.5 mm, galvanised | |
Standard colour | Doors, trims, side panels: RAL 7035, coarse structure Plinth: RAL 7012, coarse structure |
|
Optional colour | all RAL colours, fine or coarse structure | |
Layer thickness |
80-100 µm |
|
Dimensions | Height (mm, without plinth) |
2,000 / 2,200 |
Width (mm) |
400 / 500 / 600 / 850 / 1,000 / 1,200 |
|
Depth (mm) |
425 (up to 1,850 A), 625 (up to 3,200 A), 825 (from 4,000 A) |